
Paradox Magellan Systems 25
presence and functionality. If a device has not sent a signal
within the specified time period, Magellan can generate a
trouble, an alarm and/or transmit a report code to the central
monitoring station as defined by the Wireless Transmitter
Supervision Options (page 24). Sections [103] and [104]
determine which zones will be supervised and which will not.
Enable the option pertaining to the zone you wish Magellan to
supervise.
Check-in Supervision Time
Section [096]: Option [7]
Option [7] OFF = Check-in supervision time = 24Hrs
(default)
Option [7] ON = Check-in supervision time = 80 minutes
Section [096] option [7] defines the time period that
Magellan will expect a check-in status signal from the
specified wireless transmitters as defined in the Check-in
Supervision Options (page 24). If no signal is received
within the check-in supervision time, Magellan’s reaction will
be defined by the Wireless Transmitter Supervision Options
(page 24).
Panic Alarms
Section [091]: Options [1], [2] and [3]
Option [1] OFF = Panic 1 (Emergency Panic) disabled (default)
Option [1] ON = Panic 1 (Emergency Panic) enabled
Option [2] OFF = Panic 2 (Auxiliary Panic) disabled (default)
Option [2] ON = Panic 2 (Auxiliary Panic) enabled
Option [3] OFF = Panic 3 (Fire Panic) disabled (default)
Option [3] ON = Panic 3 (Fire Panic) enabled
Enable section [091] options [1], [2] and [3] to enable the
system’s three Panic alarms. Each panic alarm is activated by
pressing two keys simultaneously and holding them down for 2
seconds. See Table 8 on page 25 for the appropriate panic
alarm keys. Whether these panic alarms will generate a silent or
audible alarm is determined by section [091] options [4] to [6]
(see Panic Alarm Types on page 25).
Table 8: Panic Alarm Keys
Remote controls can also be programmed to generate panic
alarms. See Programming the Remote Control’s Buttons on
page 20 for more information on programming remote controls
to generate panic alarms.
Panic Alarm Types
Section [091]: Options [4], [5] and [6]
Option [4] OFF = Panic 1 (Emergency Panic) is silent (default)
Option [4] ON = Panic 1 (Emergency Panic) is audible
Option [5] OFF = Panic 2 (Auxiliary Panic) is silent (default)
Option [5] ON = Panic 2 (Auxiliary Panic) is audible
Option [6] OFF = Panic 3 (Fire Panic) is silent (default)
Option [6] ON = Panic 3 (Fire Panic) is pulsed
Options [4] to [6] represent the alarm types of panic alarms
1 to 3 respectively.
Silent Alarm: The Magellan console will emit a confirmation
beep and transmit the appropriate Panic report code (if
programmed in section [139]). The console will not enable
its speaker or the system siren.
Audible Alarm: Same as the silent alarm except that the
console will enable its speaker and system siren until a user
cancels the alarm (disarms) with a valid access code or
when the Bell Cut-off timer elapses (if enabled; see Bell Cut-
off Timer on page 24).
Pulsed Alarm (Fire Panic only): Same as the audible alarm
except that the siren will be pulsed as shown in Figure 15 on
page 16. Refer to Standard 24Hr. Fire Zones on page 16 for
more information on a pulsed siren output.
Keys to press Panic Alarm Type
[1] and [3] Panic 1 (Emergency Panic)
[4] and [6] Panic 2 (Auxiliary Panic)
[7] and [9] Panic 3 (Fire Panic)
Komentáře k této Příručce